The Barcelona incident (19.09.2026)

The AIMsight documentation makes it its main regression case: roadmap, line 33 and §15; support context, §7-8 (example file, question "Why did D-300-A jump?"), §12.2, §16.1 and the example "Barcelona reference switching". Its data are in data/CLARIDEN/ ("L9 BCN" export, from 17/09 22:00 to 20/09 21:50 UTC, 10-minute rate, 29 sensors including 5 references; 432 images at 10 min, one per measurement, zip times in UTC) and, coded, in case E-004 (events/E-004/).

What is observed

According to the blind report of 2026-10-15 (agent-diagnostic/rapports/2026-10-15T1346Z_CLARIDEN_19-09-matin/), rechecked on the data:

  • around 00:00 on 19/09, the references move relative to each other (PR-291 and PR-293 by +0.7 px in relative_x, D-302-C motionless); sigma0 is multiplied by ten; corr_x of the targets drops without their raw position moving;
  • at 06:10, the "-B" targets move alone in the image (0.8 to 1.4 px), the references motionless; PR_BG jumps by 17 px, its reflector is no longer visible, its error_value stays just under the threshold and its values (~11) are kept;
  • from 06:40 to 07:30, the 29 sensors move together (+1.8 to +4 px in y), then partly come back; corr_y keeps a step until the end of the measurements: +0.5 to +1.2 on the "-A" targets, growing with the distance to the references, and −1.0 on D-306-B;
  • no external cause on the images.

Two readings

  • AIMsight documentation: movement of the station and the camera, instability of the references (PR_284, PR_291), switches between compensation states, targets that remained measurable; "primarily reference-network / compensation-state instability, not target tracking". The follow-up described is on the system side: pattern reset, reconfiguration, exclusion of PR_284 considered, reference added.
  • Expert (reported by the user on 2026-10-15): the structure moved, and the camera and the references with it; the system probably overestimates the amplitude; other measurement systems on the site saw a major anomaly, and the site was interrupted; the structure is a bridge, whose arch is sagging (user, 2026-10-24). This is the diagnosis of E-004: monitored-object motion, real movement, intervention.

The two do not exclude each other: an unstable compensation distorts the amplitude of a real movement. The measurements alone do not separate the structure from the camera when everything moves together; blind, the diagnostic agent concluded a weak/unstable reference solution, consequence undetermined.

Consequences and questions

  • For the correction of the curves (D-044): these jumps are, for the expert, a real movement; do not remove them as an artifact. The amplitude, however, is not established.
  • Open: the documentation speaks of an SFTP export at 1 min and images at 15 min, here 10 min: is it the same set, reprocessed or not? PR-284 is here only a local reference (pattern_type ref), outside the compensation.